HRV Not Working in Winnipeg? Here's What to Check First
No airflow, wet windows, a frozen core or a noisy unit: match the symptom to the cause, run the free checks and know when it needs a technician.
When an HRV or air exchanger misbehaves in a Winnipeg winter, the cause is often a clogged filter, a hood blocked with snow or frost, or a humidity setting that is wrong for the weather. Those take minutes to check. Others, like a core that keeps freezing or an unbalanced unit, need a technician. This page covers an HRV or ERV that has stopped, is moving little air, is icing up or is leaving moisture on the windows. Turn the power off before you open the unit.
Find Your Symptom
| What you notice | Most likely cause | Who fixes it |
|---|---|---|
| HRV not running at all | Control off, unplugged, tripped breaker | You to start with; a technician if the breaker trips |
| Little or no airflow at the grilles | Clogged filter, blocked hood, frozen core, closed damper or loose duct | You |
| Condensation on windows | Humidity too high for the outdoor temperature | You: adjust the humidity control |
| Frozen core or ice in the unit | Defrost not keeping up, blocked filter, or unbalanced airflow | You to thaw it; a technician if it returns |
| Air too dry, static, scratchy throat | Running too fast or humidity control set too low | You |
| Water on the floor or wet duct insulation | Blocked drain or a punctured duct jacket | You, then a technician |
| Unusual noise or vibration | Dirt on the fan blades or furnace blower noise | You, then a technician |
| Runs at one speed only, or cold drafts | Control fault, or the fresh air outlets need relocating | Technician |
HRV Not Working or Not Running: Checks to Run First
- The control. Make sure the wall control is on and set to the right mode.
- Power. Check that the unit is plugged in and the cord is undamaged.
- Breaker. If a breaker has tripped or a fuse has blown, call a contractor. Natural Resources Canada says not to reset it until the cause is found, because it can be a fire or shock hazard.
HRV Little or No Airflow
Work through these in order:
- Clear both outdoor hoods of snow, frost, leaves or debris, and check the ducts to the hoods.
- Clean or replace the filters.
- Check for ducts or registers blocked or closed, such as a shut damper or a toy in a duct.
- Look at the core for frost or ice.
- Check ducts for leaks or disconnected joints and tape loose seams. Make sure the unit door is closed tight and the gaskets are sealed.
If you have done all that and the airflow is still weak, call a contractor.
HRV Condensation on Windows
Water on the windows means the indoor air holds more moisture than the outdoor temperature allows. Natural Resources Canada says to adjust the dehumidistat to limit condensation on cold surfaces. In order:
- Lower the humidity setting. The colder it is outside, the lower it should be: see the Winnipeg HRV winter settings table.
- Cut moisture at the source: run bathroom and kitchen fans, and reduce indoor drying and extra humidifiers.
- Run the HRV at a higher speed.
- Check that the HRV is moving air properly with the trash bag test below.
If condensation continues, Natural Resources Canada says the unit's minimum continuous ventilation rate may be too low for your house, which a contractor can fix. Wet or iced duct insulation points to a damaged jacket; see below.
HRV Frozen: What to Do
Most HRVs have an automatic defrost that starts when the incoming air falls below about -5°C, and the colder it gets, the longer the defrost runs. If the core still freezes, Natural Resources Canada says to:
- Open the unit door and let the ice melt. On some units the core slides out and can be thawed in a sink.
- Check and clean the filters.
- Follow your manual to check the defrost mechanism or preheater, if your model has one.
- Call a contractor if it keeps happening. The system may need rebalancing to raise the exhaust flow or lower the supply flow.
One Broan and vanEE manual says to turn the unit off during very heavy snowstorms. Frost on the core and iced door locks can also come from positive pressure, which pushes moist indoor air out through the walls.
HRV Drain and Water Problems
If there is water at the unit, pour two or three litres of warm water into the pan. When it does not flow freely, clear the drain with a piece of thin wire. The drain tubing must have a trap so air cannot be pulled in through it. Dripping or ice on a duct means a puncture in the insulation jacket: repair small punctures with foil duct tape, and replace wet or damaged insulation and reseal it.
HRV Noise and Vibration
Dirt on the fan blades is the first thing to check: brush or vacuum it off gently with the power off. If your HRV shares the furnace ducts, the furnace blower running at its higher heating speed can be loud, and Natural Resources Canada says an efficient ECM motor allows quiet low-speed running. Grinding, rattling or a vibration that persists is a job for a technician.
HRV Air Too Dry
Static and a scratchy throat mean the HRV is removing more moisture than you want. Raise the humidity setting and run the unit on its lowest speed or intermittently. Natural Resources Canada says dry air can also mean the HRV is oversized or running too fast. Check that the exhaust is not blocked and the core is not frozen.
How Do I Know if My HRV Is Working? The Trash Bag Test
Tape a large trash bag around a coat hanger and hold it over the exhaust hood outside; time how long it takes to fill. Then hold the inflated bag over the intake hood and time how long it takes to empty. On a balanced system the two times match to within a few seconds. Natural Resources Canada calls this a rough check, not a measurement.
If a furnace, water heater or fireplace is spilling fumes, or a carbon monoxide alarm sounds, do not rely on the HRV. Natural Resources Canada says combustion by-products escaping into the house mean the appliance or its venting must be repaired immediately, and a badly unbalanced HRV can make that worse by pulling the fumes back in.
When to Call a Technician
Call if the breaker trips, the core keeps freezing, airflow is weak after the checks above, condensation or dryness will not settle, or the unit is noisy or runs at one speed only. A technician can measure and rebalance the airflow, test the defrost and check the electrical parts. A service costs about $60 to $150 as an add-on, or $100 to $200 as its own visit; see HRV maintenance in Winnipeg. If the unit is beyond repair, HRV installation and replacement cost in Winnipeg shows what a new one costs. Natural Resources Canada advises against skipping a repair to save money, because a neglected system can bring poor air quality and moisture problems.
Directory · 2 companies
Winnipeg companies that list HRV work
These top-rated Winnipeg companies state HRV work on their own websites. Other listed companies may also do this work, so ask them. Tap one to open its Google listing, with phone number, hours and recent reviews.
-
View on Google
Tradesman Mechanical Services
Winnipeg mechanical contractor for furnaces, air conditioning, heat pumps, water heaters, refrigeration and electrical.
-
View on Google
Fair Service Heating & Air Conditioning
20+ years in Winnipeg and BBB A+ rated. Furnaces, air conditioning and water heaters.
Frequently Asked Questions
Check that the control is on, the unit is plugged in and the breaker has not tripped. Then clean the filters and clear the outdoor hoods. If it still will not run, or the breaker trips again, call a technician.
The indoor humidity is too high for the outdoor temperature. Lower the humidity setting, run the HRV on a higher speed and cut moisture sources. If it persists, the unit may not be ventilating enough for the house.
Frost builds on the core in cold weather when the defrost cannot keep up, often because of dirty filters, a blocked hood or unbalanced airflow. Open the door and let the ice melt, clean the filters, and call a contractor if it comes back.
Usually a clogged filter, a hood blocked by snow or frost, a closed damper or a frozen core. Clear those first; if there is still little airflow, a duct may be loose or the unit needs service.
Dirt on the fan blades or the furnace blower at high speed. Clean the blades, and call a technician if the noise or vibration continues.
The HRV may be running too fast or the humidity control is set too low. Raise the setting and run it on low or intermittently. An ERV, which recovers some moisture, can help in an extremely dry winter.
Only as a stopgap. Thaw it, clean the filters and have the airflow balance checked. One Broan and vanEE manual says to turn the unit off in very heavy snowstorms.
HRV service is about $60 to $150 as an add-on to a furnace or duct cleaning, and about $100 to $200 as its own visit. Filters are about $20 to $60 for most units. A replacement unit installed on existing ducts is typically about $1,500 to $2,800.